Compressor Application Manual
21
6.2 - EM electromechanical relay
6.2.1 - With the relay in any position,
check if there is continuity
between relay terminals 1 and 2.
If not, change the relay.
IV
Figure 15 - EM relay
6.2.2 - With the relay in the vertical
position, relay coil upwards,
check if there is continuity
between relay terminals 1 and 3.
If not, change the relay and
repeat item 6.2.1.
6.2.3 - With the relay in the vertical
position, coil downwards, check if
there is continuity between
terminals 1 and 3. If there is,
change the relay.
Figure 16 - EM relay
1
3
4
2
1
3
4
2